How To Use This Lab
1. Choose Practice or Test
Practice: Select a radio button to create that fault. Observe the changes, take measurements, and select another fault to try something else. “No fault” restores normal simulated operation.
Test: A hidden fault is created for you. Use the meter to determine the problem, select one radio-button repair, then click Make repair. A wrong repair leaves the fault in place. New test problem loads another hidden fault. The small Hint button appears in Test only and suggests a type of measurement—not the answer.
2. Set the multimeter
Click one of the clearly marked settings around the meter dial: V~ (AC voltage), Ω (resistance), • ))) (audible continuity), or OFF. The meter's display responds to the setting, your probes, and the circuit condition.
3. Place the red and gray probes
Next to each available electrical contact are two small circles. Click the red circle to place the red probe there or the gray circle for the COM probe. You can put both probes on one test point. Click Clear probes to remove them.
4. Disconnect and isolate components
Click a blue female spade to unplug its wire from a switch or gas-valve terminal; click it again to reconnect. Click the beige Molex plug to disconnect or reconnect both wires together. When a connection is unplugged, test points are available on the fixed male blades and the separate female wire ends.
Use Reconnect everything to restore manually disconnected connectors. This does not diagnose or repair a hidden scenario fault.
5. Read voltage, resistance and continuity
Use V~ to investigate energized sections and voltage drops. Switch furnace power OFF before using Ω or continuity. Closed wires and contacts normally have low resistance. A disconnected path can show OL. A continuity beep sounds only below the meter's simulated beep threshold, so a complete path through the 60 Ω gas-valve coil may not beep.
6. Check the meter probes
Click Test Probes to bring the probe tips together in a popup over the diagram. Select your own meter mode: Ω should read near zero with good leads, continuity should beep, and V~ should read zero. This test is separate from the furnace circuit. Click Clear inside the popup to close it. The result will indicate whether the probes are good or need replacing when faulty lead scenarios are added.
7. Furnace power, heat call, flame and Error Code
Use Furnace power ON and Call for heat ON to control operating conditions. R glows amber with power; W glows with power and a heat call. The flame represents a functioning energized gas-valve circuit. If a fault prevents operation during a heat call, the control board displays a blinking Error Code.
Use Power Reset on the board to clear the displayed error briefly. If the problem still exists, the code returns after 2 seconds. Resetting does not bypass an open safety or fix a failed component.
Tip: The goal is to explain the measurements and identify the fault—not to guess from the component illustrations.